Caratteristiche principali
- Commutazione precisa isocrona a tutte le temperature
- Nessun rimbalzo tra contatti
- Circuito di commutazione indipendente, separato galvanicamente
- Segnale in uscita continuo analogico per tenuta di gas
- Segnale di uscita del sensore senza deriva a lungo termine
Descrizione
The hybrid gas density monitor combines self-acting monitoring with high-performance microswitches and continuous density measurement of insulating gases in one device. It covers demanding applications and maintains highest accuracy over a very wide temperature range. Trend analysis helps to detect possible leakages sooner, provides data for preventive maintenance measures and therefore facilitates compliance with greenhouse gas regulations. This precise and maintenance-free hybrid density monitor is reliable in operation over decades for indoor and outdoor applications.
Dati tecnici
| Codice del prodotto | 878x |
|---|---|
| Categoria | Hybrid Gas Density Monitor with analogue output |
| Principio di misura | Mechanical monitoring: Principle: Reference gas measurement Electronic monitoring: Principle: Oscillating quartz measurement |
| Designazione dell'applicazione | Gas Density Monitor for SF6 and other gases with output signal for continuous monitoring |
| Segnale di uscita | Mechanical monitoring: floating change-over contact Electronic monitoring/Sensor: analogue: 6.5...20 mA current loop Output signal 6.5...20 mA current loop 0...0.85MPa absolute SF6 @ 20°C 0...56.1 kg SF6 /m3 |
| Temperatura ambiente | -40°C ... 80°C |
Downloads Go to file Downloads
Specifica tecnica:
Manuale:
-
H73515h 878x Gas Density Monitoren
pdf 1003.9KB
Non hai trovato le informazioni sul prodotto che stavi cercando? Si prega di contattare il nostro team di vendita.