«Simple Apparatus» conformity to ATEX 414 – Industat

Features

  • Compact design
  • Rugged housing
  • Protection IP65
  • Any mounting position possible
  • May be used as „simple apparatus“ in zones at risk of explosions
Product request

Downloads

×
This is a mandatory field
Please enter your email address!
CAPTCHA image for SPAM prevention If you can't read the word, click here.

Technical Data

Applications

Potentially hazardous areas

Category

Potentially hazardous areas

Dielectric strength

1.25 kV terminal ground

Approval / conformity

EN60730-1/ EN60730-2-9: Typ 2.B.H
EN60079-0, EN60079-11 Zone 1 and 2, 21 and 22

Media temperature

-30°C ... +350°C

Ambient temperature

Range ≤ +45°C: -30°C ... +50°C
Range > +45°C: -30°C ... +65°C
(important: Temperature at sensor may not exceed maximum sensortemperature)

Shock

50 g / 11 ms

Protection

IP65

Output signal

Floating change-over contact

Measuring range

-30°C ... +40°C to +70°C ... +350°C

Vibration

5...25 Hz: ±1.6 mm
25...100 Hz: 4g