M2S 104/114 Alterostat

Back to overview

Main features

  • With 1 adjustable step between 2 stages
  • Short response time
  • Protection IP54
  • Electrical connection on terminal screw
About

Technical Data

More Information
Product code 104/114
Name M2S
Designation Alterostat
Product category

Thermostats

Measuring range -30°C ... +40°C to +70°C ... +350°C
Applications

HVAC
Machine tools
Process technology
Refrigeration

Repeatability ± 0.5 % FS typ.
Designation of application Multistage thermostat with remote sensor
Approval / conformity EN60730-1/ EN60730-2-9: Type 2.B.H
Output signal Floating change-over contact
Ambient temperature Range ≤ +45°C: -30°C ... +50°C Range +45°C ... +250°C: -30°C ... +70°C Range > + 250°C: -10°C ... +70°C (Important: Temperature at sensor may not exceed maximum sensortemperature)
Standard variants of this product
Grouped product items
Product Name Temperature range [°C] Sensor max. [°C]

M2S95

+5 ... +95

105

Sensor: Capillary tube with remote sensor
Largest stage difference: 35
Set point adjustment: Internal switchpoint adjustment
Sensor material: Copper
Type Code: 114 1120 322 19

M2S150

+20 ... +150

165

Sensor: Capillary tube with remote sensor
Largest stage difference: 40
Set point adjustment: Internal switchpoint adjustment
Sensor material: Copper
Type Code: 114 1131 122 19

M2S350S

+70 ... +350

380

Sensor: Capillary tube with remote sensor
Largest stage difference: 80
Set point adjustment: Internal switchpoint adjustment
Sensor material: 1.4435 (AISI316L)
Type Code: 114 1154 021 19

M2S230S

+20 ... +230

250

Sensor: Capillary tube with remote sensor
Largest stage difference: 70
Set point adjustment: Internal switchpoint adjustment
Sensor material: 1.4435 (AISI316L)
Type Code: 114 1124 021 19

M2S35

0 ... +35

50

Sensor: Capillary tube with remote sensor
Largest stage difference: 15
Set point adjustment: Internal switchpoint adjustment
Sensor material: Copper
Type Code: 114 1109 422 19

M2S40

-30 ... +40

45

Sensor: Capillary tube with remote sensor
Largest stage difference: 25
Set point adjustment: Internal switchpoint adjustment
Sensor material: Copper
Type Code: 114 1101 422 19
Related products

Trafag is where you are

Please get in touch with us